Coleman 5151C Spezifikationen Seite 9

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 28
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 8
9
SPECIAL CLOSET INSTALLATIONS
Furnace to Closet Door Clearance Greater th an 1 Inch and Less than 6 In ch es
Figure 4 Furnace to Closet Door Clearance 1” to 6”
As an option to the lower grill,
an undercut of 2 1/2” will provide
50 Sq. In. of free area.
Clearance Greater than 1 Inch and
Less than 6 Inch es
A. The closet door MUST have a minimum
of 250 Square Inches of free area in the
upper half of the door and a minimum of
50 Square Inches of free area in the low-
er area of the door.
The lower closet door grille may be
omitted if an undercut of 2 1/2 Inches is
provided in the door.
B. A fully louvered closet door MUST have a
minimum of 250 Square Inches of free
area in the upper half of the door
.
Furnace to Closet Door Clearance Less than 1 Inch
Figure 5 Furnace to Closet Door Clearance Less than 1”
Clearance L ess than 1”
The closet door MUST have three return air grilles.
The total free area of the two upper grilles must be
a minimum of 250 Square Inches. The total free
area of the lower grille MUST be a minimum of 50
Sq. In.
NOTE: Each grille MUST BE ALIGNED directly
opposite the corresponding return air grille of
the furnace door.
Seitenansicht 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 27 28

Kommentare zu diesen Handbüchern

Keine Kommentare